When enabling SFC forces, the system displays erroneous information (4041343, 4177971, 4177979, 4177981)

Controllers
First Known in Firmware Revision
Corrected in Firmware Revision
Compact GuardLogix® 5380 SIL 2
33.011
35.017, 36.014, 37.013, 38.011 and later
Compact GuardLogix 5380 SIL 3
32.013
35.017, 36.014, 37.013, 38.011 and later
GuardLogix 5580
33.011
35.017, 36.014, 37.013, 38.011 and later

When enabling SFC forces under the following conditions:
• An SFC routine is present.
• The controller has a safety signature.

The Studio 5000 Logix Designer application displays this message: "Failed to enable SFC forces in the controller. Controller not in correct mode."

Similarly, when attempting to disable SFC forces, the following message appears:"Failed to disable SFC forces in the controller. Controller not in correct mode."

Additionally, the FORCE LED on the front of the controller does not light up amber.

Despite these messages, SFC forcing functions as expected.