This release corrects the following anomalies.
PanelView 800 terminal first-load screen refresh rate delay (APBCPV800-472)
Corrected Anomaly as of Firmware Revision 8.014
Known Anomaly first identified as of Firmware Revision 8.012
Catalog Numbers:
When PanelView™ 800 terminal is communicating with a Micro800™ programmable controller (2080-LCxx), a delay in value display is observed at PanelView 800 terminal first-load screen.
PanelView 800 terminal communication through Modbus TCP fails (APBCPV800-474)
Corrected Anomaly as of Firmware Revision 8.014
Known Anomaly first identified as of Firmware Revision 8.012
Catalog Numbers:
PanelView™ 800 terminal communication through Modbus TCP fails when Modbus device ID is changed from default value of 1.
PanelView 800 terminal displays an error for application MVRTE.exe (APBCPV800-476)
Corrected Anomaly as of Firmware Revision 8.014
Known Anomaly first identified as of Firmware Revision 8.012
Catalog Numbers:
PanelView™ 800 terminal intermittently displays an error message "Application MVRTE.exe encountered a serious error and must shut down" and requires the terminal to be restarted.
Recipe restore function failed when communicating with a MicroLogix 1400 controller (APBCPV800-490)
Corrected Anomaly as of Firmware Revision 8.014
Known Anomaly first identified as of Firmware Revision 8.013
Catalog Numbers:
Recipe restore function fails with an error message "1021 Recipe Restore failed" when:
This release has the following application notes.
Firmware and Software Compatibility
See the following application notes for firmware and software compatibility.
|
Project Version
(Project File) |
PanelView™
800 Firmware
Revision
(HMI Terminal) |
Open with Connected
Components
Workbench™ Software
Version 20.01 and
Download to PanelView
800 Graphic Terminal
(User Action) |
Open with
Connected
Components
Workbench Software
Version 21.01 and
Download to
PanelView 800
Graphic Terminal
(User Action) |
Open with Connected
Components
Workbench Software
Version 22 and
Download to
PanelView 800 Graphic
Terminal
(User Action) |
|
7.011
|
7.011
|
No issue
|
No issue(1)
|
No issue(1)
|
|
7.011
|
8.012
|
Error - If the
device/protocol in the
project file is not
supported in firmware
revision 8.012
|
Error(1) - If the
device/protocol in the
project file is not
supported in firmware
revision 8.012
|
Error(1) - If the
device/protocol in the
project file is not
supported in firmware
revision 8.012
|
|
7.011
|
8.012
|
No issue - If the
device/protocol in the
project file is supported
in firmware revision
8.012
|
No issue(1) - If the
device/protocol in the
project file is
supported in firmware
revision 8.012
|
No issue(1) - If the
device/protocol in the
project file is supported
in firmware revision
8.012
|
|
8.012
|
7.011
|
Not applicable (since the
firmware revision 8.012
project file cannot be
opened with Connected
Components Workbench
software version 20.01)
|
Not applicable (since
the firmware revision
8.012 project file
cannot be opened with
Connected
Components
Workbench software
version 21.01)
|
Not applicable (since the
application version
incompatible)
|
|
8.012
|
8.012
|
Not applicable (since the
firmware revision 8.012
project file cannot be
opened with Connected
Components Workbench
software version 20.01)
|
Not applicable (since
the firmware revision
8.012 project file
cannot be opened with
Connected
Components
Workbench software
version 21.01)
|
No issue
|
|
7.011
|
8.013
|
Error - If the
device/protocol in the
project file is not
supported in firmware
revision 8.013
|
Error(1) - If the
device/protocol in the
project file is not
supported in firmware
revision 8.013
|
Error(1) - If the
device/protocol in the
project file is not
supported in firmware
revision 8.013
|
|
7.011
|
8.013
|
No issue - If the
device/protocol in the
project file is supported
in firmware revision
8.013
|
No issue(1) - If the
device/protocol in the
project file is
supported in firmware
revision 8.013
|
No issue(1) - If the
device/protocol in the
project file is supported
in firmware revision
8.013
|
|
8.011
|
8.013
|
Not applicable (since the
firmware revision 8.011
project file cannot be
opened with Connected
Components Workbench
software version 20.01)
|
No issue(1)
|
No issue(1)
|
|
8.012
|
8.013
|
Not applicable (since the
firmware revision 8.012
project file cannot be
opened with Connected
Components Workbench
software version 20.01)
|
Not applicable (since
the firmware revision
8.012 project file
cannot be opened with
Connected
Components
Workbench software
version 21.01)
|
No issue
|
|
7.011
|
8.014
8.015 |
Error - If the
device/protocol in the
project file is not
supported in firmware
revision 8.014
|
Error(1) - If the
device/protocol in the
project file is not
supported in firmware
revision 8.014
|
Error(1) - If the
device/protocol in the
project file is not
supported in firmware
revision 8.014
|
|
7.011
|
8.014 8.015
|
No issue - If the
device/protocol in the
project file is supported
in firmware revision
8.014
|
No issue(1) - If the
device/protocol in the
project file is
supported in firmware
revision 8.014
|
No issue(1) - If the
device/protocol in the
project file is supported
in firmware revision
8.014
|
|
8.011
|
8.014 8.015
|
Not applicable (since the
firmware revision 8.011
project file cannot be
opened with Connected
Components Workbench
software version 20.01)
|
No issue(1)
|
No issue(1)
|
|
8.012
|
8.014 8.015
|
Not applicable (since the
firmware revision 8.012
project file cannot be
opened with Connected
Components Workbench
software version 20.01)
|
Not applicable (since
the firmware revision
8.012 project file
cannot be opened with
Connected
Components
Workbench software
version 21.01)
|
No issue
|
(1) No changes are made to the project file.