Release Notes

PanelView 800 (2711R-xx)
Version 8.014 (released 1/2025)

Catalog Number PanelView 800 

These release notes describe version information for PanelView 800, version 8.014 (released 1/2025).

Corrected Anomalies in This Release

This release corrects the following anomalies.

PanelView 800 terminal first-load screen refresh rate delay (APBCPV800-472)

Corrected Anomaly as of Firmware Revision 8.014

Known Anomaly first identified as of Firmware Revision 8.012

Catalog Numbers:

When PanelView™ 800 terminal is communicating with a Micro800™ programmable controller (2080-LCxx), a delay in value display is observed at PanelView 800 terminal first-load screen.

PanelView 800 terminal communication through Modbus TCP fails (APBCPV800-474)

Corrected Anomaly as of Firmware Revision 8.014

Known Anomaly first identified as of Firmware Revision 8.012

Catalog Numbers:

PanelView™ 800 terminal communication through Modbus TCP fails when Modbus device ID is changed from default value of 1.

PanelView 800 terminal displays an error for application MVRTE.exe (APBCPV800-476)

Corrected Anomaly as of Firmware Revision 8.014

Known Anomaly first identified as of Firmware Revision 8.012

Catalog Numbers:

PanelView™ 800 terminal intermittently displays an error message "Application MVRTE.exe encountered a serious error and must shut down" and requires the terminal to be restarted.

Recipe restore function failed when communicating with a MicroLogix 1400 controller (APBCPV800-490)

Corrected Anomaly as of Firmware Revision 8.014

Known Anomaly first identified as of Firmware Revision 8.013

Catalog Numbers:

Recipe restore function fails with an error message "1021 Recipe Restore failed" when:

Application Notes

This release has the following application notes.

Firmware and Software Compatibility

See the following application notes for firmware and software compatibility.

Project Version
(Project File)
PanelView™ 800 Firmware Revision
(HMI Terminal)
Open with Connected Components Workbench™ Software Version 20.01 and Download to PanelView 800 Graphic Terminal
(User Action)
Open with Connected Components Workbench Software Version 21.01 and Download to PanelView 800 Graphic Terminal
(User Action)
Open with Connected Components Workbench Software Version 22 and Download to PanelView 800 Graphic Terminal
(User Action)
7.011
7.011
No issue
No issue(1)
No issue(1)
7.011
8.012
Error - If the device/protocol in the project file is not supported in firmware revision 8.012
Error(1) - If the device/protocol in the project file is not supported in firmware revision 8.012
Error(1) - If the device/protocol in the project file is not supported in firmware revision 8.012
7.011
8.012
No issue - If the device/protocol in the project file is supported in firmware revision 8.012
No issue(1) - If the device/protocol in the project file is supported in firmware revision 8.012
No issue(1) - If the device/protocol in the project file is supported in firmware revision 8.012
8.012
7.011
Not applicable (since the firmware revision 8.012 project file cannot be opened with Connected Components Workbench software version 20.01)
Not applicable (since the firmware revision 8.012 project file cannot be opened with Connected Components Workbench software version 21.01)
Not applicable (since the application version incompatible)
8.012
8.012
Not applicable (since the firmware revision 8.012 project file cannot be opened with Connected Components Workbench software version 20.01)
Not applicable (since the firmware revision 8.012 project file cannot be opened with Connected Components Workbench software version 21.01)
No issue
7.011
8.013
Error - If the device/protocol in the project file is not supported in firmware revision 8.013
Error(1) - If the device/protocol in the project file is not supported in firmware revision 8.013
Error(1) - If the device/protocol in the project file is not supported in firmware revision 8.013
7.011
8.013
No issue - If the device/protocol in the project file is supported in firmware revision 8.013
No issue(1) - If the device/protocol in the project file is supported in firmware revision 8.013
No issue(1) - If the device/protocol in the project file is supported in firmware revision 8.013
8.011
8.013
Not applicable (since the firmware revision 8.011 project file cannot be opened with Connected Components Workbench software version 20.01)
No issue(1)
No issue(1)
8.012
8.013
Not applicable (since the firmware revision 8.012 project file cannot be opened with Connected Components Workbench software version 20.01)
Not applicable (since the firmware revision 8.012 project file cannot be opened with Connected Components Workbench software version 21.01)
No issue
7.011
8.014
8.015
Error - If the device/protocol in the project file is not supported in firmware revision 8.014
Error(1) - If the device/protocol in the project file is not supported in firmware revision 8.014
Error(1) - If the device/protocol in the project file is not supported in firmware revision 8.014
7.011
8.014
8.015
No issue - If the device/protocol in the project file is supported in firmware revision 8.014
No issue(1) - If the device/protocol in the project file is supported in firmware revision  8.014
No issue(1) - If the device/protocol in the project file is supported in firmware revision 8.014
8.011
8.014
8.015
Not applicable (since the firmware revision 8.011 project file cannot be opened with Connected Components Workbench software version 20.01)
No issue(1)
No issue(1)
8.012
8.014
8.015
Not applicable (since the firmware revision 8.012 project file cannot be opened with Connected Components Workbench software version 20.01)
Not applicable (since the firmware revision 8.012 project file cannot be opened with Connected Components Workbench software version 21.01)
No issue

(1) No changes are made to the project file.

  
Rockwell Automation recognizes that some of the terms that are currently used in our industry and in this publication are not in alignment with the movement toward inclusive language in technology. We are proactively collaborating with industry peers to find alternatives to such terms and making changes to our products and content. Please excuse the use of such terms in our content while we implement these changes.

Copyright © 2026 Rockwell Automation, Inc. All rights reserved.
Rockwell Automation, Allen-Bradley, and FactoryTalk are trademarks of Rockwell Automation, Inc.
To view a complete list of Rockwell Automation trademarks please click here.
Trademarks not belonging to Rockwell Automation are property of their respective companies.