This release has the following requirements.
Firmware Requirements 8.001
System Requirement First Identified as of Firmware Revision 8.001
Catalog Numbers: PanelView™ 5310, PanelView 5510
This release includes the following system features.
Web Browser
System Feature First Identified as of Firmware Revision 8.001
Catalog Numbers: PanelView™ 5510
An HTML5 capable web browser for the PanelView 5510 is capable of displaying content on an SD card or USB drive locally to the panel, on an intranet server, or on the Internet. The PanelView 5310 does not support the web browser. The new Open Web Browser command displays the web browser as a full window or a smaller window overlaying another screen. Configure allowed locations by role to limit the URLs allowed to display in the browser. Typical use cases include:
500 Screen Support
System Feature First Identified as of Firmware Revision 8.001
Catalog Numbers: PanelView™ 5310, PanelView 5510
The PanelView 5510 now displays up to a total of 500 screens and popups. The PanelView 5310 is limited to a total of 100 screens and popups. There is no longer a limitation of 50 popups. Many performance improvements were implemented for Studio 5000 View Designer® and the PanelView 5000 runtime.
Automatic Diagnostics
System Feature First Identified as of Firmware Revision 8.001
Catalog Numbers: PanelView™ 5310, PanelView 5510
The Automatic Diagnostics feature works with Logix controllers at revision v33 and later to automatically provide fault information about your Rockwell Automation control system. If devices connected to the Logix controller experience fault conditions, the Logix controller will automatically send this information to the PanelView 5000, making it easier to notice and troubleshoot fault conditions. If you use the predefined screens and system banner indication, Studio 5000 View Designer® does not require any configuration.
• New indicator on system banner shows when faults occur.
• New Automatic Diagnostics summary element lists any current diagnostic notifications.
• Automatic Diagnostics messages support language switching to Portuguese, French, Italian, German, Spanish, Chinese, Japanese, and Korean.
• New Automatic Diagnostics history element shows past 1000 diagnostic events.
Clear Specific Data Log
System Feature First Identified as of Firmware Revision 8.001
Catalog Numbers: PanelView™ 5310, PanelView 5510
This functionality extends the Clear Data Log command with the ability to clear a single data log.
Keypad Location Configuration
System Feature First Identified as of Firmware Revision 8.001
Catalog Numbers: PanelView™ 5310, PanelView 5510
Numeric inputs have a new property for KeypadPosition to define where on the screen the keypad displays.
This release corrects the following anomalies.
Tags Appear in Error on the Emulator
Corrected Anomaly with Firmware Revision 8.001
Bulletin Numbers: PanelView™ 5510, and PanelView 5310
Tags appear in error on the Emulator if items are modified in the Browse for Controller dialog (155926).
Tags appear in error on the Emulator with an error message of Read … failed because a CIP connection could not be made if items are modified in the Browse for Controller dialog used to browse for an Emulator to Controller Path. To resolve this issue, close the Emulator, browse for the Emulator to Controller Path, and launch the Emulator again. (155926)
PDF Viewer Refresh
Corrected Anomaly with Firmware Revision 8.001
Bulletin Numbers: PanelView™ 5510, and PanelView 5310
Deleting and re-adding a PDF document from a project does not automatically refresh an instance of a PDF Viewer (153526).
Deleting and re-adding a PDF document from a project does not automatically refresh an instance of a PDF Viewer Add-On Graphic that references the PDF document. Close and reopen the project or screen containing the PDF Viewer Add-On Graphic, or select a different PDF document in the PDF Viewer Add-On Graphic and then reselect the re-added PDF document in the PDF Viewer Add-On Graphic.
Properties Pane of a Shortcut
Corrected Anomaly with Firmware Revision 8.001
Bulletin Numbers: PanelView™ 5510, and PanelView 5310
Properties pane of a shortcut does not show a newly-added user-defined data type property definition when the shortcut is open (145474).
Adding an initial user-defined data type property definition to a screen when a shortcut to the screen is open does not immediately show the new property on the Properties pane of the shortcut. Select the defining screen tab again and then reselect the shortcut tab. Alternatively, close and reopen the shortcut or click within the Project Explorer.
Hyper-V Virtual Machine Emulator Instance
Corrected Anomaly with Firmware Revision 8.001
Bulletin Numbers: PanelView™ 5510, and PanelView 5310
Emulator instance appears smaller than expected after rebooting a Hyper-V Virtual Machine (153276).
Rebooting a Hyper-V Virtual Machine with View Designer installed or shutting down View Designer without first closing the VM window causes the first instance of the Emulator that opens after the reboot or restart to appear smaller than expected. Close and restart the Emulator.
Not All Elements Display
Corrected Anomaly with Firmware Revision 8.001
Bulletin Numbers: PanelView™ 5510, and PanelView 5310
Too many elements on the screen results that not all of them display. (862116).
If multiple elements on a screen have state tables with many states and many of the properties of the elements are included in the state table, then some of the elements may not be visible on the screen. To work around this anomaly, use fewer properties in the state tables or have a smaller number of states.
This release has the following known anomalies.
Popup Windows Containing Multiple Add-on Graphics Open Slowly in Subsequent Interactions (4176857)
|
Products
|
First Known in
Firmware Revision
|
Corrected in
Firmware Revision
|
|
PanelView™ 5310
|
8.001
|
10.002 and later
|
|
PanelView 5510
|
8.001
|
10.002 and later
|
Complex popup windows that reference multiple add-on graphics open slowly after the first time they are opened.
Partial Frame Appears Around PDF
Known Anomaly First Identified as of Firmware Revision 8.001
Bulletin Numbers: PanelView™ 5510, and PanelView 5310
Partial frame appears around PDF document displayed on the HMI device (1069225).
The PDF viewer from Toolbox > System may have a partial frame around the PDF document on the HMI device.
Slower Read Times
Corrected Anomaly with Firmware Revision 9.001
Known Anomaly First Identified as of Firmware Revision 8.001
Bulletin Numbers: PanelView™ 5310
.dmk File's Digital Signature Verification Fails
Known Anomaly First Identified as of Firmware Revision 8.001
Bulletin Numbers: PanelView™ 5510, and PanelView 5310
The .dmk file's digital signature verification fails when using ControlFLASH Plus (1339133).
When flashing the HMI device, ControlFLASH Plus returns an error failing to validate the digital signature of the .dmk file. This anomaly exists when using ControlFLASH Plus version 4.00. A future version of ControlFLASH Plus will resolve this anomaly.
These anomalies are from previous releases but are still known in this release.
Controller Tag Reference
Corrected Anomaly with Firmware Revision 9.001
Known Anomaly First Identified as of Firmware Revision 3.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
Projects referencing a controller with more than the recommended limit of 50,000 tags may experience a restart of the HMI device when performing an online synchronization with the controller. [DFCTS00361416]
Reference a controller with no more than 50,000 tags.
Issues When Using ControlFLASH During Screen Change
Known Anomaly First Identified as of Firmware Revision 3.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
The use of ControlFLASH™ to update the firmware on the HMI device while the HMI device is changing screens can cause the following anomalies:
[DFCTS00356235]
If the firmware update fails, use the ControlFLASH again to complete the firmware update. If the HMI device faults, restart the HMI device and use the ControlFLASH again to complete the firmware update.
To avoid this anomaly, update the firmware on the HMI device when the HMI device is not changing screens.
Error When Number of Alarms is Exceeded
Known Anomaly First Identified as of Firmware Revision 3.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
An HMI device screen error occurs when the number of alarms exceeds the recommended value. [DFCTS00361167]
To resolve this issue, do not exceed 1,000 alarms.
Data Logging
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
If you eject and immediately reinsert the SD card into the HMI device, data logging might not restart. Data logging does not recognize that the SD card is present. Eject the SD card, wait several seconds, and reinsert the SD card to restart data logging. [46846]
Aliased Logix Designer Tags
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
The HMI device does not display passed-through extended properties of aliased Logix Designer tags. [DFCTS00350204]
Error When Binding to Module-defined Tags
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
A binding to a module-defined tag shows an invalid syntax error on the HMI device when adding the module online. [DFCTS00360870]
Enumerated Properties
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
Enumerated properties that are bound to a string tag do not work if the content of the string tag, including case, does not match the enumeration on the user interface. For example, the rounding property value Nearest does not equal nearest. [DFCTS00351889]
To resolve this issue, make sure that the letter casing for bound properties matches the casing for properties on the user interface.
State Enter Event Does Not Trigger
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
When two or more shortcuts navigate to the same screen and that screen has a State Table and a State Enter event, navigation from a shortcut triggers the State Enter event. When immediately navigating from the open shortcut to another shortcut that also represents the same screen, the State Enter event does not trigger. [DFCTS00361627]
Events on Alarm Table
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
The Events tab is visible when selecting an Alarm table graphic element. Alarm table graphic elements have built-in events. By adding events to an alarm table graphic element, the built-in events can stop working. [DFCTS00360544]
Do not add events to an alarm table graphic element.
Download While Screen Saver Is Running
Known Anomaly First Identified as of Firmware Revision 5.001
Bulletin Numbers: PanelView™ 5510 and PanelView 5310
When downloading to an HMI device on which the screen saver is running, there is no indication that the download is occurring, and the Home screen, rather than the last open screen, appears on the HMI device when the download is complete. [DFCTS00342409]
SD Card Corrupt File System
Known Anomaly First Identified as of Firmware Revision 5.001
Bulletin Numbers: PanelView™ 5510 and PanelView 5310
SD cards formatted with FAT32 can corrupt the file system on the SD card if the HMI device loses power while data logging.
To work around this issue, use an SD card formatted with EXT3. [57822]
Repeated Disconnect and Reconnect
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
If the network between the PanelView 5500 terminal and the Logix controller disconnects for less than 3 seconds or repeatedly disconnects and reconnects, the PanelView 5500 project can occasionally resynchronize with the Logix controller project. Depending on the size of your project, this resynchronization can cause tag values and alarms to take up to a few minutes to start showing values again after the network is reconnected. Any data values show one of these error messages:
[DFCTS00363667]
During this time, no alarms appear on the PanelView 5500 terminal.
Button Behavior
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
The release action for Button Behavior events, which a touch press or key press triggers simultaneously, execute when the first touch or key releases. This action occurs even when the other touch or key is still pressed. [DFCTS00354276]
ShelveDuration and MaxShelveDuration Values
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
The ShelveDuration and MaxShelveDuration values for an alarm are not updated if the values are changed through a numeric input from the HMI device. The previous values are used instead. [DFCTS00339713]
To change ShelveDuration and MaxShelveDuration for an alarm, use Logix Designer.
Trend Chart
Corrected Anomaly with Firmware Revision 9.001
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510 and PanelView 5310
Pausing a trend chart can cause some traces to no longer appear. This can occur when pausing and resuming a trend chart immediately after a download or screen navigation. The data does not appear if the trend chart has a higher sample rate than the data log. The trend chart plots only historical data for the sample period. [1353612]
Inconsistent Synchronization Indications and Tag Communication Errors
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
Inconsistent synchronization indications and tag communication errors can appear on the HMI device when the Logix controller is almost out of memory. [47168]
Tertiary DNS Configuration
Corrected Anomaly with Firmware Revision 9.001
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
When the HMI device automatically obtains IP settings by using DHCP, the system tag ::Local:HMIDevice.Enet[0].TertiaryDNSConfig does not update to reflect the tertiary DNS configuration that is obtained through DHCP. To display the tertiary DNS configuration that is obtained through DHCP, use the system tag ::Local:HMIDevice.Enet[0].TertiaryDNS. [1353622]
Conflicting Error Messages
Known Anomaly First Identified as of Firmware Revision 5.001
Bulletin Numbers: PanelView™ 5510 and PanelView 5310
Downloading a project containing a tag with a syntax error or invalid format displays conflicting error messages. An incorrect message appears stating that the tag does not exist in the controller or has an External Access property set to None. The correct error message appears in the Errors pane. [59562]
@AlarmSet Values
Known Anomaly First Identified as of Firmware Revision 5.001
Bulletin Numbers: PanelView™ 5510 and PanelView 5310
Reading .@AlarmSet values at a controller or program level from a version 31 Logix controller displays an error message. The HMI device cannot immediately read .@AlarmSet values at a controller or program level from a version 31 Logix controller.
To work around this issue, wait several seconds after opening the page with the graphic element that displays the .@AlarmSet values. The correct values appear. [150257]
Read Fails Tag Does Not Exist or External Access Property Set to None
Known Anomaly First Identified as of Firmware Revision 5.001
Bulletin Numbers: PanelView™ 5510 and PanelView 5310
A graphic element bound to an array element or structured tag member that does not exist can display an incorrect error message on the HMI device when the read fails. The incorrect error states that the read fails because the tag does not exist in the controller or has an External Access property set to None. The read actually fails because even though the parent tag exists, the binding specifies an array element or structure member which does not exist.
To work around this issue, bind to an existing array element or structured tag member. [59562]
No Tag Values In Alarm Annunciation
Known Anomaly First Identified as of Firmware Revision 5.001
Bulletin Numbers: PanelView™ 5510 and PanelView 5310
When displaying a version 31 Logix controller tag-based alarm in the In Alarm state on a PanelView 5000 HMI device, and the Use and evaluate alarm configuration is disabled and then enabled, no associated tag values appear in the alarm annunciation.
To work around the issue, update the Logix controller to version 32. [159028]
Screen Errors When Exceeding Recommended Alarm Limits
Known Anomaly First Identified as of Firmware Revision 6.001
Bulletin Numbers: PanelView™ 5500, PanelView 5510, and PanelView 5310
An HMI device screen error occurs when the number of alarms exceeds the recommended value. [4092]
To resolve this issue, do not exceed 4,000 alarms per controller.
Traces Not Appearing
Corrected Anomaly with Firmware Revision 9.001
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5510 and PanelView 5310
Pausing a trend chart can cause some traces to no longer appear. This can occur when pausing and resuming a trend chart immediately after a download or screen navigation. The data does not appear if the trend chart has a higher sample rate than the data log. The trend chart plots only historical data for the sample period. [1353612]
Synch and Communication Errors
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5510 and PanelView 5310
Inconsistent synchronization indications and tag communication errors can appear on the HMI device when the Logix controller is almost out of memory. [2582]
Events on Alarm Tables
Known Anomaly First Identified as of Firmware Revision 4.001
Bulletin Numbers: PanelView™ 5510 and PanelView 5310
The Events tab is visible when selecting an Alarm table graphic element. Alarm table graphic elements have built-in events. Adding events to an alarm table graphic element can cause the built-in events to stop working. [DFCTS00360544]
Do not add events to an alarm table graphic element.
Download Failure
Known Anomaly First Identified as of Firmware Revision 6.001
Bulletin Numbers: PanelView™ 5510 and PanelView 5310
A Windows 7 anomaly may cause a project download to fail with a message that View Designer cannot connect to the HMI device.
See Rockwell Automation Knowledgebase Answer ID 2588507 and install the hotfix. [2605]
Project Cannot Download
Known Anomaly First Identified as of Firmware Revision 3.001
Bulletin Numbers: PanelView™ 5510 and PanelView 5310
A project that is open in View Designer version 3.01 that does not have a .vpd extension cannot download to the HMI device when both View Designer version 3.01 and version 4.01 or later are installed on the same computer.
Rename the project file to end in the extension .vpd. [2397]
Elements Not Visible On The Screen
Known Anomaly First Identified as of Firmware Revision 7.001
Bulletin Numbers: PanelView™ 5510 and PanelView 5310
If multiple elements on a screen have state tables with many states and many of the properties of the elements are included in the state table, then some of the elements may not be visible on the screen.
To work around this anomaly, use fewer properties in the state tables or have a smaller number of states. [6572]
HMI Devices Pause Data Updates
Known Anomaly First Identified as of Firmware Revision 7.001
Bulletin Numbers: PanelView™ 5510 and PanelView 5310
When using CompactLogix 5370 controllers running version 33 firmware, rapidly repeating network disruptions may cause PanelView 5000 HMI devices to intermittently pause updating data for two or three seconds at a time.
If this issue occurs, cycle power to the switches in your network, or manually disconnect and reconnect ports. [5395]
Parameterized Popups
Corrected Anomaly with Firmware Revision 7.002
Known Anomaly First Identified as of Firmware Revision 7.001
Bulletin Numbers: PanelView™ 5510 and PanelView 5310
Corrected: Anomaly where parameterized popups did not update tag data correctly when repeatedly displayed with the same tag instances.
This release has the following functional changes from the previous release.
Improved View Designer Performance
Functional Change First Identified as of Firmware Revision 8.001
Catalog Numbers: PanelView™ 5510 and PanelView 5310
View Designer performance was improved in these functions:
• Save
• Find/replace
• Open a project
• Launching the emulator
• Renaming an AOG definition
Runtime performance was improved for:
• Screen switching
• Downloads
Images are now limited in size to avoid performance issues.
Popup Caching
Functional Change First Identified as of Firmware Revision 8.001
Catalog Numbers: PanelView™ 5510 and PanelView 5310
Popup caching is now selectable using the Cacheable property on a popup.
Background Operations
Functional Change First Identified as of Firmware Revision 8.001
Catalog Numbers: PanelView™ 5510 and PanelView 5310
To launch projects faster, View Designer now performs some background operations after the project is opened instead of waiting to open the project.
• Certain operations cannot be done until these background operations are complete:
• Download
• Emulate
• Verify
• Find and Replace
• Save as .vpdr
• Background operations are indicated by blinking a new icon on the ribbon.
• When the blinking stops, background operations are complete.
This release has the following application notes.
Firewall Rules 8.001
Application Notes First Identified as of Firmware Revision 8.001
Catalog Numbers: PanelView™ 5510 and PanelView 5310
View Designer does not require endpoint firewall rules because it is not a server product that allows remote clients.
Additional security considerations when using Rockwell Automation products include:
Project Limits 8.001
Application Notes First Identified as of Firmware Revision 8.001
Catalog Numbers: PanelView™ 5510 and PanelView 5310
For best results, observe View Designer project limits:
|
Description
|
Limit
|
Notes
|
|
Number of controllers
|
1 (PanelView 5310)
4 (PanelView 5510)
|
|
|
Number of HMI devices per controller
|
4
|
|
|
Number of tag references on a single
screen
|
2000
|
|
|
Total number of tag references in a View
Designer project
|
20000
|
|
|
Number of screens and popups
|
100 for PanelView
5310 and 500 for
PanelView 5510
|
Shortcuts and pre-defined
screens do not count
towards the limit.
|
|
Number of shortcuts in a project
|
400
|
|
|
Number of alarms in a controller
|
4000 tag-based or
1000 instruction-based
|
|
|
Number of alarms in a project
|
16000 tag-based or
4000 instruction-based
|
PanelView 5310 is still
limited to 4000 tag-based or
1000 instruction-based
alarms.
|
|
Number of elements on a single screen
|
1000
|
|
|
Number of graphic elements on a single
screen
|
1000 or until reaching
memory capacity
|
|
|
Number of Add-On Graphic definitions per
project
|
500
|
|
|
Number of Add-On Graphic instances per
project
|
500 or until reaching
the 1000 tag reference
limit for a screen
|
|
|
Number of Add-On Graphic instances on a
screen
|
500 or until reaching
the 1000 tag reference
limit for a screen
|
|
|
Number of graphic elements in an Add-On
Graphic
|
250
|
|
|
Number of properties defined for an
Add-On Graphic
|
20
|
|
|
Number of tags in a controller
|
50000
|
View Designer counts every
scalar, array element,
structure member, and so
forth, as a separate tag.
|
|
Number of tags for all data logs in a project
|
250
|
|
|
Image size limit
|
10 MB
|
|
|
Number of project events per project
|
1000
|
|
|
Number of images on a screen
|
500 or memory full
|
|
|
Number of PDF viewer graphic elements
on a screen
|
2
|
|
|
Number of PDF viewers appearing
simultaneously on a screen and popup
|
2
|
|
|
Amount of metadata
|
Each analog tag
referenced is capable
of having eu/min/max.
Each BOOLEAN tag
referenced is capable
of having state
identifiers All
referenced tags are
capable of having
descriptions.
|
|
|
Number of View Designer instances open
simultaneously
|
3
|
View Designer does not
support opening the same
project in more than one
instance of View Designer.
|
|
Length of a text input
|
82 characters
|
|
|
Length of a text display reading from a
STRING data type in the controller
|
476 characters
|
Using UTF-8 for STRING
encoding may result in
displaying 476 characters
incorrectly. Each character
may take multiple bytes of
data.
|
|
Number of users defined in Security
Administration
|
500
|
|
|
Number of simultaneous VNC connections
to PV5000
|
1
|
|
|
Number of simultaneously running
Emulators
|
1
|
|
|
Number of allowed data points to log
|
1.296 billion
|
This number of data points
equals 250 data points at
500 milliseconds for 30
days.
|