Release Notes
25C... More information: PowerFlex® 527 Site
Version 2.002 (released 4/2021)
Catalog Number PowerFlex 527
These release notes describe version information for PowerFlex 527, version 2.002 (released 4/2021).
Corrected Anomalies in This Release
This release corrects the following anomalies.
M15 fault occurs during drive initialization (PCBANOM-3627)
Corrected Anomaly with PowerFlex® 527 Drives Firmware Revision 2.002
Known Anomaly First Identified as of PowerFlex 527 Drives Firmware Revision 1.001
Catalog Number: 25C
The fault "INIT FLT M15 POWER BOARD" occasionally occurs during drive initialization.
This firmware revision helps to eliminate noise in the power module ID signal.
Drive faults when starting a motor with ground fault present (PCBANOM-3043)
Corrected Anomaly with PowerFlex® 527 Drives Firmware Revision 2.002
Known Anomaly First Identified as of PowerFlex 527 Drives Firmware Revision 1.001
Catalog Number: 25C
The drive faults when you start a motor with a ground fault present.
This firmware revision helps to improves the detection of ground faults when starting a
motor.
Application Notes
This release has the following application notes.
Determine PowerFlex 527 Firmware Revision Level
Using Studio 5000 Logix Designer® Software
- Launch the Logix Designer software.
- Open the project for your PowerFlex® 527 drive.
- On the main screen, click
and select Go Online.

- Right-click on the PowerFlex 527 drive and select Properties.

- In the Module Properties window, select the Module Info tab to display the
firmware revision.

Use ControlFLASH and ControlFLASH Plus to Update Your Firmware
For instructions on how to install ControlFLASH™ and ControlFLASH Plus software and
upgrade your drive firmware by using these software tools, see these publications:
- For ControlFLASH software version 15.03 or later, see ControlFLASH User Manual, publication 1756-UM105
- For ControlFLASH Plus software version 3.01 or later, see ControlFLASH Plus
Quick Start Guide Quick Start, publication CFP-QS001
Rockwell Automation recognizes that some of the terms that are currently used in our industry and in this publication are not in alignment with the movement toward inclusive language in technology. We are proactively collaborating with industry peers to find alternatives to such terms and making changes to our products and content. Please excuse the use of such terms in our content while we implement these changes.